Description
Hioki Clamp On Sensor 9695-02 for Reliable Load Current Monitoring
The Hioki Clamp On Sensor 9695-02 is engineered for professionals who need precise and consistent AC load current measurements in commercial and industrial electrical systems. With a rated measurement current of 50 A AC and continuous operation up to 60 A, this sensor is suitable for monitoring inverter-driven equipment, control panels, and commercial power lines.
Power Meters and PQAs
This sensor features a voltage output of 10 mV per ampere, ensuring compatibility with power meters, power loggers, and power quality analyzers. When connected to supported instruments, it provides accurate measurement without disrupting circuits, enhancing safety and efficiency during field inspections and monitoring tasks.
High Accuracy Applications
With an amplitude accuracy of ±0.3 percent and phase accuracy of ±2 degrees, the Clamp On Sensor 9695-02 ensures precise readings across a wide frequency range of 40 Hz to 5 kHz. Its performance makes it ideal for evaluating inverter systems, commercial power distribution, and load monitoring for industrial equipment.
Compact Spaces
The sensor’s compact and lightweight design allows it to fit into confined wiring paths and panel layouts. It supports insulated conductors up to 15 mm in diameter, making it practical for use in tight electrical enclosures and narrow conduit runs.
Daily Electrical Maintenance
Durable and easy to handle, the sensor operates reliably within 0°C to 50°C and 80% relative humidity. Optional connection cable 9219 facilitates flexible installations for field measurements or temporary monitoring, making it a versatile tool for engineers, technicians, and maintenance teams.
Technical Specifications Table
| Specification | Details |
| Product Name | Clamp On Sensor 9695-02 |
| Measurement Type | AC load current |
| Rated Measurement Current | 50 A AC |
| Maximum Measurement Current | Continuous 60 A |
| Output Signal | 10 mV AC per ampere |
| Amplitude Accuracy | ±0.3% rdg ±0.02% f.s. |
| Phase Accuracy | ±2° |
| Frequency Characteristics | 40 Hz to 5 kHz |
| Max Rated Voltage to Earth | 300 V AC rms or less |
| Measurable Conductor Diameter | 15 mm or less |
| Operating Temperature | 0°C to 50°C |
| Dimensions | 50.5 mm W × 58 mm H × 18.7 mm D |
| Weight | 50 g |
| Output Terminal | M3 terminal (3 mm) |
| Compatible Instruments | Power meters, PQAs, LR5051 clamp logger |
| Optional Accessory | Connection cable 9219 |
Click here to learn more about similar products from HIOKI E E CORPORATION