CLAMP ON POWER HiTESTER 3286 -20

CLAMP ON POWER HiTESTER 3286 -20

$709.95

Single-Phase and Three-Phase Handheld Power Meter with Harmonic Analysis Up to 20th Order

 

REQUEST A QUOTE



Description

Hioki clamp meters are best in class handheld current and voltage meters for safely and accurately measuring power lines. The 3286-20 can measure voltage, current, power, power factor, phase angle, reactive power or frequency, as well as detect phase sequence on live lines at any desired point of a single-phase circuit or three-phase circuit. CLAMP ON POWER HiTESTER 3286

3286-20

Note: The 3286-20’s three-phase power measurement method calculates and displays the power values for a sine wave input at 50/60 Hz, assuming it is balanced and there is no distortion. Accurate measurement is not possible on a three-phase line if it is not balanced, for example when controlled by an inverter or thyristor. Since there is no integration function, it is not possible to measure total energy consumed (Wh).

CETrueRMS

CAT III 600 V

Key Features CLAMP ON POWER HiTESTER 3286

• Measure single-phase 600 kW lines and up to the 20th harmonic level

• Active/ reactive/ apparent power, power factor, phase detection, frequency, harmonic waveform value, or waveform peak value

• Simple checking of three-phase lines (balanced with no distortion)

■ Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)

 

Measurement line

 

Single-phase, Three-phase (balanced with no distortion)

 

Measurement items

 

Voltage, Current, Voltage/current peak, Active/ reactive/ apparent power, Power factor, Phase angle, Reactivity, Frequency, Voltage/current harmonic levels

 

Voltage ranges 30 – 1kHz

 

150.0 V to 600 V, 3 ranges
Basic accuracy: ±1.0 % rdg. ±3 dgt. (at 45 – 66 Hz, True RMS)

 

Current ranges 45 – 1kHz

 

20.00 A to 1000 A, 3 ranges
Basic accuracy: ±1.3 % rdg. ±3 dgt. (at 45 – 66 Hz, True RMS)

 

Power ranges 80 – 600 V 1 – 1000 A

 

[Single phase] 3.000 kW to 600.0 kW
Basic accuracy: ±2.3 % rdg. ±5 dgt. (at 50/60 Hz, Power factor = 1)
[Balanced three phase] 6.000 kW to 1200 kW
Basic accuracy: ±3.0 % rdg. ±10 dgt. (at 50/60 Hz, Power factor = 1)

 

Harmonic levels

 

Voltage/current harmonic levels up to 20th, Content factor, Total harmonic distortion ratio

 

Other functions

 

[Phase angle] Forward 90.0 ° to 0 to delay 90.0 °
[Power factor] Forward 0 to 1.000 to delay 0
[Frequency] 30.0 Hz to 1000 Hz
Waveform peak, Phase detection, Max. / Min. value record, Data hold, Auto power off, RS-232C output (Options are discontinued, so cannot use RS-232C)

 

Display

 

LCD, Max. 6000 digits, Display refresh rate: 1 time/s (Normal) 1 time/3s (Slow), 1 time/2s (Harmonic level)

 

Power supply

 

Stacked alkaline battery (6LR61, 6LF22) ×1, Continuous use: 25 hours
 

Core jaw dia.

 

φ 55 mm (2.17 in) or 80 mm (3.15 in) × 20 mm (0.79 in) bus-bar

 

Dimensions and mass

 

100 mm (3.94 in) W × 287 mm (11.3 in) H × 39 mm (1.54 in) D, 650 g (22.9 oz)

 

Accessories

 

Carrying Case 9245 × 1, Voltage Cord L9635-01 × 1, Hand strap × 1, Stacked alkaline battery (6LF22) × 1, Instruction manual × 1

Get in touch with us to inquire about our tailored consulting services.