Power Demand Analyzer Custom 5000A Kit

Power Demand Analyzer Custom 5000A Kit

$3,495.00

REQUEST A QUOTE
SKU: 3169-20-01/5000 Category:



Description

Hioki portable power meters and analyzers are best in class power measuring instruments for measuring single to three-phase lines with a high degree of precision and accuracy. The 3169 is clamp on power meters designed to measure demand and harmonics, which are important for energy management, as well as basic electrical parameters such as voltage, current, power, power factor, and integrated power (watthours). Power Demand Analyzer Custom 5000A Kit

3169-20 basic model
3169-21 with D/A output function model

Note: Optional current sensor is necessary to measure current or power parameters. To store measurement data, use only the guaranteed PC cards sold by Hioki.

RS232CCETrueRMS

Key Features Power

• Simultaneously measure demand and harmonic waveforms that share the same voltage line over 4-circuits

• Save data to a PC card

• High-speed and continuous processing to measure individual waveforms

• High-speed D/A output for analog graph recording (Model 3169-21)

■ Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)

 

Measurement line & number of circuits

 

Single-phase 2-wires (4 circuits), Single-phase 3-wires (2 circuits), Three-phases 3-wires (2 or 1 circuit), and Three-phases 4-wires (1 circuit)
Note: 50 or 60 Hz, and that share the same voltage line

 

Measurement items

 

Voltage, Current, Active/ reactive/ apparent power, Active/ reactive power integration, Power factor, Frequency, Harmonic waveform value (up to 40th order)

 

Measurement range

 

[Voltage] 150.00 V to 600.00 V AC, 3 ranges, [Current] 500.00 mA to 5.0000 kA AC (depends on current sensor in use), [Power] 75.000 W to 900.00 kW (depends on combination of voltage, current range, and measurement line)

 

Basic accuracy

 

AC Voltage: ±0.2 % rdg. ±0.1 % f.s.
AC Current: ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy
Active power: ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy (at power factor = 1)
Clamp on sensor 9661: ±0.3 % rdg. ±0.01 % f.s. (different from each sensor models)

 

Measurement method

 

Digital sampling, PLL synchronization or 50/60 Hz fixed clock

 

Display refresh rate

 

2 times /sec (except when a PC card accessing, or RS-232C communications)

 

Data save interval

 

Standard interval: 1 sec to 30 sec, 1 minute to 60 minutes, 13 selects
Fast interval: A single waveform, or 0.1, 0.2, or 0.5 sec (at instant value only)

 

Frequency characteristics

 

Fundamental waveforms up to the 50th order ±3% f.s. + measurement accuracy (of a 45 to 66 Hz fundamental waveform)

 

Other functions

 

Error connect check, language selection, display hold, setting backup, power shut off management, key lock, [3169-21 only] D/A output 4 channels, (±5 V DC f.s.)

 

Power supply

 

100 to 240 V AC, 50/60 Hz, 30 VA max.

 

Dimensions and mass

 

210 mm (8.27 in)W × 160 mm (6.30 in)H × 60 mm (2.36 in)D, 1.2 kg (42.3 oz)

 

Accessories

 

Voltage cord L9438-53 ×1 (Black/ Red/ Yellow/ Blue, 3 m (9.84 ft) length, Alligator clip ×4), Power cord ×1, Instruction manual ×1, Quick start manual ×1, CD-R ×1 (RS-232C interface operating manual) ×1, Input cord label ×1, Connection cable 9441 ×1 (for the 3169-21 only)